products

Air to Air Sensible Plate Heat Exchanger-BXB series

Air to Air Sensible Plate Heat Exchanger-BXB series(图1)

Structural characteristics of

 

·BXB sensible heat exchanger can be made of seawater corrosion resistant hydrophilic aluminum plate, epoxy resin aluminum plate or stainless steel plate;

· The heat transfer surface of the heat exchanger was strengthened by heat transfer stamping, and the heat transfer area was increased by 10%-12%;

· The heat exchange sheet adopts enhanced punching and biting technology, with higher strength, better sealing, and air leakage rate less than 1%;

· The air passage is supported by a conductor convex cylinder with a high pressure difference capacity of 2500Pa for new exhaust;

· The normal service temperature of ordinary aluminum foil is not higher than 100℃; the temperature resistance of special sealing material can be up to 200℃; the temperature resistance of stainless steel can be 350℃;

· Tap water or neutral washing liquid can be used for direct cleaning, which is easy to use and easy to maintain;

· Different plate spacing (2.0mm-10.0mm) and any combination length can be provided.

application

·AC Ventilation System

·Room Ventilation System

·Industrial Ventilation System

·Heat Pump Drying System

·Indirect Evaporative Cooling System

·Large-scale Scientific Breeding Bystem

·Purify Air Conditioning Fresh Air System

·Wind Generator Air to Air Indirect Cooling System

·Heat Recovery in Winter

·Cold Recovery in Summer

When to Specify a Sensible Plate Core (BXB)

  • Best for: sensible-only recovery in clean ventilation and HVAC loops; pairs with AHUs and fresh-air units.
  • Not for: latent (humidity) recovery — use a total/enthalpy plate or wheel for that. For contaminated industrial exhaust, keep the streams isolated with a plate, never a wheel.

BXB Sensible Plate Core

The BXB is a fixed-plate, sensible-only air-to-air core: it transfers heat but not moisture. That makes it simple, robust, and cheap to maintain for ventilation where humidity recovery is not required.

Sensible vs Total Recovery

If you also need to recover moisture, use a total (enthalpy) plate or a wheel. For most ventilation and make-up air where dry heat recovery is enough, a sensible plate is the right, lower-cost choice. See sensible vs total recovery for the full comparison.

Construction and Specs

  • Counter-flow or cross-flow aluminum or stainless plates.
  • No moving parts, no carryover between streams.
  • Easy to clean; can be washed down for light-duty lines.

Applications

Commercial fresh-air units, AHUs, data-center make-up air, and any clean ventilation loop. For contaminated or hygiene-sensitive exhaust, keep the streams isolated with a plate rather than a wheel.

Related: plate heat exchanger (PHE), AHU with heat recovery.